Why does the local/remote button not work on the ATV212 drive?

Issue:
ATV212 local/remote button is not working.

Product Line:
Altivar 212, ATV212

Environment:
All

Cause:
N/A

Resolution:
The button might have been disabled. To check this:

  1. From 0.0, press mode and arrow down to F---.
  2. Press enter and arrow up to F732.
  3. Press enter and make sure it is set to 0 (enabled).