What are the switchgear control failure codes in Easergy T300?
Published date:
23 April 2019
Whenever a command is issued a code appears in the event log for each control operation. These are the following codes and the reasons indicating the status of each control operation.
CODE
REASON
0
Command completed successfully
1
Local command blocked because switch position is intermediate or unknown
2
Local command blocked because switch position is already in correct state
3
Local command cancelled by user
4
Switch position did not change within configured maximum operation time
5
Command blocked by Head Unit interlocks, e.g. motor supply fault or battery low
6
Command failed due to timeout waiting for enable from Head Unit
7
Local command blocked because disabled by configuration
8
Local command blocked because local/remote status is unknown
9
Local command blocked because local/remote status is remote
10
Local command blocked because automation is ON
11
Remote command blocked because automation is ON
12
Sectionalizer command blocked because automation is OFF
13
Sectionalizer command blocked because local/remote status is unknown
14
Sectionalizer command blocked because local/remote status is remote
15
Unexpected command source (firmware error)
16
Remote command blocked because requested position is not a valid value
17
Command blocked because a command is already in progress for this module
18
Command blocked because the power shutdown signal is active
19
Command blocked because a command is already in progress for another module
20
Command blocked because measured switch position is intermediate or unknown
21
Command blocked because measured switch position is same as the requested position
22
Command blocked because earth switch position is not closed
23
Open command blocked because external input is false
24
Open command blocked because external input is true
25
Close command blocked because external input is false
26
Close command blocked because external input is true
27
Commands blocked because module behaviour mode is OFF