{}

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric corporate Website

Search FAQs
Are there any EMC filters for C2 category for drives supplied by 690V?
690V supply network is not public network for residential environment. It is industrial network and typically supplied by distribution transformer which is part of installation.
So mains with 690V is typically 2nd environmnent (C3 or C4) therefore this additional EMC filter is not necessary. From this point of view we do not offer additional EMC filters for 690V drives.

Schneider Electric Global

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: