Browse FAQs

Why are my ATV340 parameters lost when I cycle power if I've written them over the network?

Published date: 21 July 2020

​Issue: 
Parameters lost when power cycling

Product Line:
Altivar ATV  Process Drive
 
Environment:
ALL
 
Cause:
Programming Wiring
 
Resolution:
 After you program with the PLC you have to toggle bit 1 of the CMI word to save the parameters to the EEProm or they revert when power is cycled.

Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.