Where do you wire in remote speed reference to an ATV660?

Published date: 03 April 2020

Issue:
Where do you land customer wires for remote speed reference to an ATV660?

Product Line:
ATV660

Environment:
ALL

Cause:
Wiring / Programming

Resolution:

Customer Contacts for external analog input control signal. 
TB1-11 = COM / Neutral
TB1-12 = AI3 Signal wire (programmable for 0-10, factory set for 4-20ma)
Program under :  Complete Settings > Inputs/Outputs > AI/AQ tab > AI3 Configuration

 