What causes a PID Feedback Error on an Altivar Process Drive?
Published date:
24 June 2019
Issue: My Process drive tripped and shows PFMF PID Feedback Error
Product Line: Altivar Process Drive
Environment: ALL
Cause: Wiring / Programming
Resolution:
Rapid changes in flow like a Valve opened, so it will run full speed. While valve remains open the drive shuts down on PFMF PID Feedback Error, because the loop is now open. Go to Pump Functions Feedback Monitoring Feedback Monitoring and change to NO.
Can't find what you are looking for?
Reach out to our customer care team to receive information on technical support, assistance for complaints and more.