How to monitor RAM battery voltage on RemoteConnect?

Published date: 20 October 2019

To monitor the RAM battery voltage, use System Analog Point ‘SYS_INFO_MemoryBatteryVoltage’ that point will indicate the device battery voltage in real format.
 
Another way to indicate low battery is alarm using below system points,
 
  • SYS_INFO_NVretentionAlert with data type ‘Digital’ used with firmware 9.1.1 or earlier only
             False = Normal
             True = Alert (Lithium battery low)
 
  • SYS_INFO_MemoryBatteryAlert with data type ‘Digital’ used with firmware 9.1.2 or later only
             False = Normal
             True = Alert (Lithium battery low)
 