Welcome to the Schneider Electric corporate Website

Select your location

Welcome the the Schneider Electric French website. It looks like you are located in the United States, would you like to change your location?

Traduisez en francais
View all   TeSys SK
Schneider Electric LC1SKGC301G7 Image
Discontinued

LC1SKGC301G7

Schneider Electric LC1SKGC301G7 Image
Discontinued
LC1SKGC301G7

TeSys SK mini contactor - 3P (3 NO) - AC-3 - 690 V 9 A - 120 V AC coil

Show more characteristics
LC1SKGC301G7 has not been replaced. Please contact your customer care center for more information.
The maximum number of products that can be compared is 4. Remove already added products.

  • Main
    range
    TeSys
    product name
    TeSys SK
    product or component type
    Mini contactor
    device short name
    LC1SKGC
    contactor application
    Motor control
    Resistive load
    utilisation category
    AC-1
    AC-3
    power pole contact composition
    3P
    pole contact composition
    3 NO
    [Ue] rated operational voltage
    Power circuit: 690 V AC 50/60 Hz
    Signalling circuit: 690 V AC <= 400 Hz
    [Ie] rated operational current
    20 A (at <50 °C) AC AC-1
    9 A at <= 400 V AC AC-3
    motor power kW
    4 kW at 380...415 V AC 50/60 Hz
    4 kW at 660...690 V AC 50/60 Hz
    1.1 kW at 220...230 V AC 50/60 Hz
    control circuit type
    AC at 50/60 Hz
    [Uc] control circuit voltage
    120 V AC 50/60 Hz
    auxiliary contact composition
    1 NC
    [Ith] conventional free air thermal current
    20 A (at 55 °C) for power circuit
    10 A (at 55 °C) for signalling circuit
    Irms rated making capacity
    85 A AC conforming to NF C 63-110
    85 A AC conforming to IEC 60947
    rated breaking capacity
    68 A at <= 400 V conforming to NF C 63-110
    68 A at <= 400 V conforming to IEC 60947
    [Icw] rated short-time withstand current
    60 A 55 °C for power circuit
    associated fuse rating
    20 A gI at <= 440 V for power circuit
    10 A gI for signalling circuit conforming to IEC 60947
    10 A gI for signalling circuit conforming to VDE 0660
    average impedance
    4 mOhm - Ith 20 A 50 Hz for power circuit
    [Ui] rated insulation voltage
    Power circuit: 690 V conforming to BS 5424
    Power circuit: 690 V conforming to IEC 60947
    Power circuit: 690 V conforming to UL 508
    Power circuit: 690 V conforming to VDE 0110 group C
    Power circuit: 690 V conforming to CSA C22.2 No 14
    mounting support
    Rail
    Panel
    standards
    IEC 60947
    VDE 0660
    BS 5424
    NF C 63-110
    product certifications
    CULus
    connections - terminals
    Connector 1 cable(s) 1.5…6 mm²solid
    Connector 2 cable(s) 1.5…4 mm²solid
    Connector 1 cable(s) 0.5…6 mm²flexible without cable end
    Connector 2 cable(s) 0.35…2.5 mm²flexible without cable end
    Connector 1 cable(s) 0.35…6 mm²flexible with cable end
    Connector 2 cable(s) 0.35…1.5 mm²flexible with cable end
    tightening torque
    Power circuit: 0.8 N.m - on connector - with screwdriver pozidriv No 1
    operating time
    6...8 ms coil de-energisation and NO opening
    7...14 ms coil energisation and NO closing
    8...16 ms coil energisation and NC opening
    8...10 ms coil de-energisation and NC closing
    mechanical durability
    10 Mcycles
    maximum operating rate
    1200 cyc/h
    Complementary
    control circuit voltage limits
    Operational: 0.85...1.1 Uc at 50/60 Hz (at <55 °C)
    Drop-out: 0.2...0.75 Uc at 50/60 Hz (at <55 °C)
    inrush power in VA
    23 VA 50/60 Hz (at 20 °C)
    hold-in power consumption in VA
    4.9 VA 50/60 Hz (at 20 °C)
    heat dissipation
    1.5 W at 50/60 Hz
    signalling circuit frequency
    <= 400 Hz
    Environment
    IP degree of protection
    IP2x conforming to VDE 0106
    protective treatment
    TC conforming to IEC 60068
    TC conforming to DIN 50015
    ambient air temperature for operation
    -20…50 °C
    ambient air temperature for storage
    -50…70 °C
    operating altitude
    2000 m without derating
    height
    58 mm
    width
    45 mm
    depth
    56 mm
    net weight
    0.175 kg
    Packing Units
    Package 1 Weight
    0.175 kg
    Package 1 Height
    0.640 dm
    Package 1 width
    0.600 dm
    Package 1 Length
    0.480 dm
    Contractual warranty
    Warranty
    18 months
  • View more View less

    Documents

    Language
    • All Languages5
    • English5
    • French4
    Catalogue
    Format
    Size
    Date
    Add to My Documents
    TeSys - Catalogue 2020 - Innovative and connected solutions for motor starters (Version 10.0)
    Description
    Ready-to-use motor starters and all components for building specific motor starters ( circuit breakers, contactors, overload relays , accessories ...). This edition includes a presentation of the new TeSys island system. The catalogue can also be downloaded chapter per chapter.
    prp.document.label.format pdf
    Size 118.2 MB
    Date 7/22/20
    Description
    Ready-to-use motor starters and all components for building specific motor starters ( circuit breakers, contactors, overload relays , accessories ...). This edition includes a presentation of the new TeSys island system. The catalogue can also be downloaded chapter per chapter.
    CAD
    Format
    Size
    Date
    Add to My Documents
    prp.document.label.format zip
    Size 809.3 KB
    Date 3/26/14
    Files in document
    Instruction sheet
    Format
    Size
    Date
    Add to My Documents
    prp.document.label.format pdf
    Size 1.6 MB
    Date 10/1/12
    Declaration of conformity
    Format
    Size
    Date
    Add to My Documents
    prp.document.label.format pdf
    Size 285.8 KB
    Date 7/4/19
    prp.document.label.format pdf
    Size 285.8 KB
    Date 7/4/19
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.