Multi 9 - C60H-DC - MCB - 2P - 10 A - C Curve - 500 V - 5 kA

Show more characteristics
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

MGN61528 is replaced by:
Product
Qty
M9U21210
Qty
1
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4
  • Reason for Substitution: End of life
  • Substitution date: 01 January 2017
1
  • Main
    range
    Multi 9
    product name
    Multi 9 C60H-DC
    product or component type
    Miniature circuit-breaker
    device short name
    C60H-DC
    device application
    Distribution
    poles description
    2P
    number of protected poles
    2
    [In] rated current
    10 A at 25 °C
    network type
    DC
    trip unit technology
    Thermal-magnetic
    curve code
    C
    breaking capacity
    20 kA Icu at 220 V DC conforming to GB 14048.2
    10 kA Icu at 440 V DC conforming to GB 14048.2
    6 kA Icu at 500 V DC conforming to GB 14048.2
    20 kA Icu at 220 V DC conforming to EN/IEC 60947-2
    10 kA Icu at 440 V DC conforming to EN/IEC 60947-2
    6 kA Icu at 500 V DC conforming to EN/IEC 60947-2
    5 kA AIR at 12...500 V DC conforming to UL 1077
    utilisation category
    Category A conforming to EN/IEC 60947-2
    suitability for isolation
    Yes conforming to EN/IEC 60947-2
    Complementary
    [Ue] rated operational voltage
    12...500 V DC
    magnetic tripping limit
    8.5 x In +/- 20 % AC
    [Ics] rated service breaking capacity
    4.5 kA 75 % conforming to GB 14048.2 - 500 V DC
    7.5 kA 75 % conforming to GB 14048.2 - 440 V DC
    15 kA 75 % conforming to GB 14048.2 - 220 V DC
    15 kA 75 % conforming to EN/IEC 60947-2 - 220 V DC
    7.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V DC
    4.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V DC
    limitation class
    3 conforming to EN/IEC 60947-2
    [Ui] rated insulation voltage
    500 V DC conforming to EN/IEC 60947-2
    [Uimp] rated impulse withstand voltage
    6 kV conforming to EN/IEC 60947-2
    contact position indicator
    Yes
    control type
    Toggle
    local signalling
    ON/OFF indication
    mounting mode
    Clip-on
    mounting support
    DIN rail
    comb busbar and distribution block compatibility
    Top or bottom: standard
    9 mm pitches
    4
    height
    81 mm
    width
    36 mm
    depth
    73 mm
    net weight
    0.256 kg
    colour
    Grey
    mechanical durability
    20000 cycles
    electrical durability
    3000 cycles L/R = 2 ms
    6000 cycles
    provision for padlocking
    Padlockable
    locking options description
    In position O
    connections - terminals
    Tunnel type terminal (top or bottom)1…25 mm² (AWG 18...AWG 4) - rigid stranded
    Tunnel type terminal (top or bottom)1…16 mm² (AWG 18...AWG 6) - flexible
    Tunnel type terminal (top or bottom)1…16 mm² (AWG 18...AWG 6) - flexible with ferrule
    Tunnel type terminal (top or bottom) - 2 cable(s) 1…10 mm² (AWG 18...AWG 8) - rigid stranded
    Tunnel type terminal (top or bottom) - 2 cable(s) 1…10 mm² (AWG 18...AWG 8) - flexible
    Tunnel type terminal (top or bottom) - 2 cable(s) 1…10 mm² (AWG 18...AWG 8) - flexible with ferrule
    Tunnel type terminal (top or bottom) - 3 cable(s) 1 mm² (AWG 18) - flexible stranded
    wire stripping length
    14 mm for top or bottom connection
    tightening torque
    2.5 N.m top or bottom
    earth-leakage protection
    Without
    Environment
    standards
    UL 1077
    GB 14048.2
    EN/IEC 60947-2
    product certifications
    UR
    CCC
    IEC
    IP degree of protection
    IP20 conforming to IEC 60529
    IP40 (modular enclosure) conforming to IEC 60529
    pollution degree
    3 conforming to EN/IEC 60947-2
    overvoltage category
    IV
    tropicalisation
    2 conforming to IEC 60068-2
    2 conforming to GB 14048.2
    relative humidity
    95 % at 55 °C
    operating altitude
    2000 m
    ambient air temperature for operation
    -25…70 °C
    ambient air temperature for storage
    -40…85 °C
    Contractual warranty
    Warranty
    18 months