Welcome to the Schneider Electric corporate Website

Select your location

View all   Zelio Timer Relays
Schneider Electric RE11LHBM Image
Discontinued

RE11LHBM

Schneider Electric RE11LHBM Image
Discontinued
RE11LHBM

on-delay timing relay - 1 s..100 h - 24..240 V AC/DC - solid state output

Show more characteristics
The maximum number of products that can be compared is 4. Remove already added products.

RE11LHBM is replaced by:
Product
Qty
RE17LHBM
Qty
1
The maximum number of products that can be compared is 4. Remove already added products.
  • Reason for Substitution: End of life
  • Substitution date: 01 December 2013
1
  • Main
    range of product
    Zelio Time
    product or component type
    Modular timing relay
    discrete output type
    Solid state
    width pitch dimension
    17.5 mm
    component name
    RE11L
    time delay type
    H
    time delay range
    0.1...1 s
    1...10 s
    10...100 h
    6...60 min
    1...10 min
    1...10 h
    6...60 s
    [Us] rated supply voltage
    24...240 V AC at 50/60 Hz
    Complementary
    control type
    Selector switch front panel
    voltage range
    0.85...1.1 Us
    nominal output current
    0.7 A
    connections - terminals
    Screw terminals, 1 x 4 mm² without cable end
    Screw terminals, 2 x 1.5 mm² with cable end
    Screw terminals, 2 x 2.5 mm² without cable end
    housing material
    Self-extinguishing
    repeat accuracy
    +/- 0.5 % conforming to IEC 61812-1
    temperature drift
    +/- 0.05 %/°C
    voltage drift
    +/- 0.2 %/V
    setting accuracy of time delay
    +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
    minimum pulse duration
    0.05 s
    reset time
    350 ms on de-energisation
    on-load factor
    100 %
    power consumption in VA
    32 VA at 240 V
    breaking capacity
    0.5 A AC/DC conforming to UL
    0.7 A AC/DC at 20 °C
    maximum output current
    20 A
    minimum switching current
    10 mA
    maximum leakage current
    5 mA
    maximum switching voltage
    250 V
    maximum voltage drop
    <4 V 3-wire
    <8 V 2-wire
    electrical durability
    100000000 cycles
    mechanical durability
    100000000 cycles
    marking
    CE
    creepage distance
    4 kV/3 conforming to IEC 60664-1
    surge withstand
    1 kV differential mode conforming to IEC 61000-4-5 level 3
    2 kV common mode conforming to IEC 61000-4-5 level 3
    mounting support
    35 mm symmetrical mounting rail conforming to EN 50022
    net weight
    0.06 kg
    Environment
    immunity to microbreaks
    10 ms
    derating factor
    5 mA/°C
    dielectric strength
    2.5 V 1 mA/1 minute conforming to IEC 60255-5
    2.5 V 1 mA/1 minute conforming to IEC 60664
    standards
    EN 50081-1/2
    73/23/EEC
    89/336/EEC
    93/68/EEC
    EN 50082-1/2
    IEC 61812-1
    IEC 60669-2-3
    product certifications
    CSA
    CULus
    ambient air temperature for storage
    -30…60 °C
    ambient air temperature for operation
    -20…60 °C
    IP degree of protection
    IP20 (terminal block) conforming to IEC 60529
    IP40 (housing) conforming to IEC 60529
    IP50 (front panel) conforming to IEC 60529
    vibration resistance
    0.35 mm (f= 10…55 Hz) conforming to IEC 60068-2-6
    relative humidity
    93 % without condensation conforming to IEC 60068-2-3
    resistance to electrostatic discharge
    6 kV in air conforming to IEC 61000-4-2 level 3
    8 kV in contact conforming to IEC 61000-4-2 level 3
    resistance to electromagnetic fields
    10 V/m 80 MHz to 1 GHz conforming to ENV 50140/204 level 3
    10 V/m 80 MHz to 1 GHz conforming to IEC 61000-4-3 level 3
    resistance to fast transients
    1 kV (capacitive connecting clip) conforming to IEC 61000-4-4 level 3
    2 kV (direct) conforming to IEC 61000-4-4 level 3
    immunity to radioelectric fields
    10 V (0.15...80 MHz) conforming to ENV 50141 (IEC 61000-4-6 level 3)
    immunity to voltage dips
    30 % / 10 ms conforming to IEC 61000-4-11
    60 % / 100 ms conforming to IEC 61000-4-11
    95 % / 5 s conforming to IEC 61000-4-11
    disturbance radiated/conducted
    Class B conforming to EN 55022 (EN 55011 group 1)
    Contractual warranty
    Warranty
    18 months
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Width 17.5 mm



  • Connections and Schema

    Internal Wiring Diagram



    Wiring Diagram



  • Technical Description

    Function H : Interval Relay
    Description

    On energisation of the relay, timing period T starts and the output(s) R close(s). At the end of the timing period T, the output(s) R revert(s) to its/their initial state. The second output can be either timed or instantaneous.

    Function: 1 Output


    Function: 2 Outputs


    2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)


    Legend

    Relay de-energised

    Relay energised

    Output open

    Output closed

    C

    Control contact

    G

    Gate

    R

    Relay or solid state output

    R1/R2

    2 timed outputs

    R2 inst.

    The second output is instantaneous if the right position is selected

    T

    Timing period

    Ta -

    Adjustable On-delay

    Tr -

    Adjustable Off-delay

    U

    Supply


Compare products: /