Product FAQs

Ask a Question

Can C60HDC circuit breakers be replaced by IC60 circuit breakers for DC distribution: 12, 24 & 48VDC following tripping curves B, C & D?

Yes customer can use Acti9 iC60 range on DC networks.
There is no derating for thermal protection, and around root of 2 factor for magnetic threshold.
See details in CA908024E.
Was this helpful?
What can we do to improve the information ?