Product FAQs

Ask a Question

How to disable Ethernet protocols in ION7400, ION8650 and PM8000?

Issue
How to disable Ethernet protocols in ION7400, ION8650 and PM8000.

Product Line
PM8000
ION8650
ION7400

Environment
ION Setup 3.0

Cause
To control the available Ethernet protocols and their port numbers.

Resolution

Resolution 1: In ION Setup, in Setup Assistant, navigate to Communications -> Advanced Ethernet -> Protocols tab. Choose the Protocol that needs to be disabled. Change the Enabled for the the protocol to unchecked.



Resolution 2: In ION Setup, in Advanced mode, navigate to Comms Modules -> Ethernet -> Setup Registers tab. Choose the Protocol that needs to be disabled. Change the register for the the protocol to No

Was this helpful?
What can we do to improve the information ?