  • Main
    range of product
    Modicon Quantum automation platform
    product or component type
    AC discrete output modules
    discrete output number
    32
    Complementary
    group of channels
    4 groups of 8 channels
    supply frequency
    47...63 Hz
    voltage drop
    1.5 V
    discrete output voltage
    20...253 V AC
    addressing requirement
    2 output words
    absolute maximum output
    300 Vrms for 10 s AC
    400 Vrms 1 cycle AC
    maximum load current
    0.88 mA 230 V off state leakage per output
    1 A rms 20...253 V per output
    16 A rms per module
    4 A rms per group
    surge current
    <= 2.5 A during 1 ms
    dV/dt
    400 V/ms
    response time
    <= 0.5 ms at state 0 to state 1
    <= 0.5 ms at state 1 to state 0
    protection type
    Internal by RC filter
    Internal output protection by 4 A fuse
    power dissipation
    1.60 + (1.0 V x total module load current)
    marking
    CE
    local signalling
    1 LED green bus communication is present (Active)
    1 LED red external fault detected (F)
    32 LEDs green input status
    bus current requirement
    320 mA
    module format
    Standard
    product weight
    0.45 kg
    Environment
    product certifications
    CUL
    FM Class 1 Division 2
    standards
    CSA C22.2 No 142
    UL 508
    electromagnetic compatibility
    Electrostatic discharge immunity test (test level:4 kV, contact discharge) conforming to IEC 801-2
    Electrostatic discharge immunity test (test level:8 kV, air discharge) conforming to IEC 801-2
    Susceptibility to electromagnetic fields (test level:10 V/m, 80...1000 MHz) conforming to IEC 801-3
    ambient air temperature for operation
    0...60 °C
    ambient air temperature for storage
    -40...85 °C
    relative humidity
    95 % without condensation
    operating altitude
    <= 5000 m
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Product end of life instructions
    Available
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    Catalogue
    Date
    Size
    Add to My Documents
    User guide
    Date
    Size
    Add to My Documents
    Date 2018/07/14
    Size 9.7 MB
    Certificate
    Date
    Size
    Add to My Documents
    Date 2018/06/19
    Size 363.5 KB
    Date 2018/08/06
    Size 233.4 KB
    Declaration of conformity
    Date
    Size
    Add to My Documents
    Date 2018/06/19
    Size 233.5 KB
    Date 2018/08/06
    Size 510.4 KB
    End of life manual
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Racks for Modules Mounting
    Dimensions of Modules and Racks


    (1)
    2 slots
    (2)
    3 slots
    (3)
    4 slots
    (4)
    6 slots
    (5)
    10 slots
    (6)
    16 slots


  • Connections and Schema

    24...230 Vac Discrete Output Module
    Wiring Diagram


    N/C