insulation monitoring XM300C Vigilohm - 380..415 V AC 50/60 Hz - fail safe

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range of product
    Vigilohm
    device short name
    XM300C
    type of measurement
    Network insulation resistance, earth leakage capacitance
    signal contacts composition
    3 C/O
    earthing system
    IT
    display type
    LCD
    scale
    0.1...999 kOhm
    fail safe feature
    With
    [Us] rated supply voltage
    380...415 V AC, 50/60 Hz (tolerance: - 15...10 %)
    mounting position
    Horizontal mounting
    Complementary
    [Ue] rated operational voltage
    <= 1000 V AC, 45...400 Hz (device connected to phase with PHT1000 subassembly)
    <= 1200 V DC (device connected with PHT1000)
    <= 1700 V AC, 45...400 Hz (device connected to neutral with PHT1000 subassembly)
    <= 440 V AC, 45...400 Hz (device connected to phase)
    <= 500 V DC
    <= 760 V AC, 45...400 Hz (device connected to neutral)
    signalling function
    Alarm
    Device fault
    Insulation value display
    Transient fault
    test function
    Manual, self test
    breaking capacity
    10 A at 24 V DC, L/R = 1 ms
    0.45 A at 220 V DC, L/R = 1 ms
    0.65 A at 120 V DC, L/R = 1 ms
    2.5 A at 48 V DC, L/R = 1 ms
    5 A at 230 V AC, cos phi = 0.7
    3 A at 400 V AC, cos phi = 0.7
    power consumption in VA
    <= 30 VA
    mounting mode
    Flush-mounted
    mounting support
    Cubicle
    Enclosure
    Plate
    height
    129 mm
    width
    153 mm
    depth
    213.5 mm
    product weight
    3.5 kg
    auxiliary connection terminal
    Tunnel type terminals, cable cross section: 1.5 mm²
    Environment
    dielectric strength
    2500 V
    IP degree of protection
    IP30
    standards
    IEC 364 ch 4 and 5
    IEC 61557-8
    NF C 15-100 §413.4
    UTE C 63-080 class CPI/XA
    ambient air temperature for operation
    -5...55 °C
    ambient air temperature for storage
    -25...70 °C
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    User guide
    Date
    Size
    Add to My Documents
    CAD
    Date
    Size
    Add to My Documents
    VIGILOHM SYSTEN XM300C 115- 127VAC
    Date 2013/09/10
    Size 481.7 KB
    Date 2013/09/10
    Size 391.3 KB
    Insulation monitoring device; Vigilohm XM300
  • Technical FAQs

    No results found
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.