Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Choose another country or region

59608 Product picture Schneider Electric

View all Sepam series 20

Sepam series 20 - 59608

Base unit and accessories

59608 Product picture Schneider Electric
View all Sepam series 20

Sepam series 20 - 59608

Base unit and accessories

remote advanced UMI module DSM303 Sepam series 20, 40, 60, 80

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range of product
    Sepam series 20
    Sepam series 40
    Sepam series 80
    Sepam series 60
    device short name
    DSM303
    user machine interface type
    Remote advanced
    Complementary
    UMI indication
    Alarms and operating messages
    Protection setting
    Sepam parameter setting
    Status of logic imputs
    Version of Sepam and remote modules
    Metering and diagnosis data
    UMI control
    Alarm acknowledgement
    Output testing
    Sepam reset
    local signalling
    2 LEDs for Sepam operating status on front face
    9 LEDs for indication of parameters on front face
    height
    117 mm
    width
    152 mm
    depth
    40 mm
    product weight
    0.3 kg
    mechanical robustness
    Earthquakes in operation ( level: 2) : 1 Gn (vertical axes) conforming to IEC 60255-21-3
    Earthquakes in operation ( level: 2) : 2 Gn (horizontal axes) conforming to IEC 60255-21-3
    Jolts de-energized ( level: 2) : 20 Gn/16 ms conforming to IEC 60255-21-2
    Shocks de-energized ( level: 2) : 27 Gn/11 ms conforming to IEC 60255-21-2
    Shocks in operation ( level: 2) : 10 Gn/11 ms conforming to IEC 60255-21-2
    Vibrations de-energized ( level: 2) : 2 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1
    Vibrations in operation ( level: 2) : 1 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1
    Vibrations in operation ( level: Fc) : 2 Hz...13.2 Hz, a = +/- 1 mm conforming to IEC 60068-2-6
    Environment
    IP degree of protection
    IP52 conforming to IEC 60529
    electromagnetic compatibility
    Fast transient bursts immunity tests-conducted disturbances : IV (4kV, 2.5 kHz ) conforming to IEC 61000-4-4
    Immunity to radiated fields immunity tests-radiated disturbances : III (10 V/m, 80 MHz...2 GHz ) conforming to IEC 61000-4-3
    Disturbing field emission emission tests : A conforming to EN 55022
    Fast transient bursts immunity tests-conducted disturbances : A and B (4kV, 2.5 kHz/2 kV, 5 kHz ) conforming to IEC 60255-22-4
    Immunity to conducted RF disturbances immunity tests-conducted disturbances : III (10 V ) conforming to IEC 60255-22-6
    Conducted disturbance emission emission tests : A conforming to EN 55022
    Immunity to magnetic fields at network frequency immunity tests-radiated disturbances : IV (30 A/m (continuous)-300 A/m (1-3 s) ) conforming to IEC 61000-4-8
    Surges immunity tests-conducted disturbances : III (2 kV CM, 1 kV DM ) conforming to IEC 61000-4-5
    1 MHz damped oscillating wave immunity tests-conducted disturbances (2.5 kV CM, 1 kV DM ) conforming to IEC 60255-22-1
    1 MHz damped oscillating wave immunity tests-conducted disturbances (2.5 kV CM, 2.5 kV DM ) conforming to ANSI C37.90.1
    100 kHz damped oscillating wave immunity tests-conducted disturbances (2.5 kV CM, 1 kV DM ) conforming to IEC 61000-4-12
    Conducted disturbance emission emission tests conforming to IEC 60255-25
    Disturbing field emission emission tests conforming to IEC 60255-25
    Electrostatic discharge immunity tests-radiated disturbances (8 kV air, 4 kV contact ) conforming to ANSI C37.90.3
    Electrostatic discharge immunity tests-radiated disturbances (8 kV air, 6 kV contact ) conforming to IEC 60255-22-2
    Fast transient bursts immunity tests-conducted disturbances (4kV, 2.5 kHz ) conforming to ANSI C37.90.1
    Immunity to radiated fields immunity tests-radiated disturbances (10 V/m, 80 MHz...1 GHz ) conforming to IEC 60255-22-3
    Immunity to radiated fields immunity tests-radiated disturbances (35 V/m, 25 MHz...1 GHz ) conforming to ANSI C37.90.2
    Voltage interruptions immunity tests-conducted disturbances (100 % during 100 ms ) conforming to IEC 60255-11
    climatic withstand
    Continuous exposure to damp heat (in operation) : Cab : 10 days, 93 % RH, 40 °C conforming to IEC 60068-2-78
    Continuous exposure to damp heat (in storage) : Cab : 56 days, 93 % RH, 40 °C conforming to IEC 60068-2-78
    Continuous exposure to damp heat (in storage) : Db : 6 days, 95 % RH, 55 °C conforming to IEC 60068-2-30
    Exposure to cold (in storage) : Ab : - 25 °C conforming to IEC 60068-2-1
    Exposure to dry heat (in operation) : Bd : 70 °C conforming to IEC 60068-2-2
    Exposure to dry heat (in storage) : Bb : 70 °C conforming to IEC 60068-2-2
    Salt mist (in operation) : Kb/2 : 6 days conforming to IEC 60068-2-52
    Temperature variation with specified variation rate (in storage) : Nb : - 25 °C to 70 °C, 5 °C/min conforming to IEC 60068-2-14
    Exposure to cold : Ad : - 25 °C conforming to IEC 60068-2-1
    Influence of corrosion/gaz test 2 (in operation) : 21 days, 75 % RH, 25 °C, 0.5 ppm H2S, 1 ppm S02 conforming to IEC 60068-2-60
    Influence of corrosion/gaz test 4 (in operation) : 21 days, 75 % RH, 25 °C, 0.01 ppm H2S, 0.2 ppm S02, 0.2 ppm NO2, 0.01 ppm CI2 conforming to IEC 60068-2-60
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Product end of life instructions
    Available
  • Documents and Downloads

    Language
    • English
    Catalogue
    Date
    Size
    Add to My Documents
    Date 2018/11/06
    Size 31 MB
    User guide
    Date
    Size
    Add to My Documents
    Date 2017/12/21
    Size 8.6 MB
    Product environmental
    Date
    Size
    Add to My Documents
    Date 2017/09/21
    Size 96.7 KB
  • Technical FAQs

    No results found
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.