  • Main
    range of product
    Modicon Premium Automation platform
    product or component type
    Discrete output module
    discrete output number
    16
    discrete output type
    Relay not protected
    discrete output voltage
    12...24 V DC conforming to EN/IEC 61131-2 10...34 V
    24...240 V AC conforming to EN/IEC 61131-2 20...264 V
    Complementary
    [Ith] conventional free air thermal current
    3 A
    response time
    < 10 ms deactivation
    < 8 ms activation
    contacts type and composition
    1 NO
    output overvoltage protection
    AC inductive, by RC circuit MOV (ZNO) on each preactuator
    DC inductive, by discharge diode on each preactuator
    output overload protection
    1 external fuse per channel or group of channel fast blow
    short-circuit protection
    1 external fuse per channel or group of channel fast blow
    isalotion resistance
    > 10 MOhm 500 V
    power dissipation
    (0.25 W + 0.2 W x No of outputs at state 1)
    electrical durability
    1000000 cycles DC-12 24 W 24 V resistive
    1000000 cycles DC-3 24 W 24 V inductive
    2000000 cycles DC-3 10 W 24 V inductive
    300000 cycles DC-12 40 W 24 V resistive
    100000 cycles AC-14 220 VA 220 V inductive
    100000 cycles AC-15 220 VA 220 V inductive
    1000000 cycles AC-12 110 VA 110 V resistive
    1000000 cycles AC-12 220 VA 220 V resistive
    1000000 cycles AC-12 50 VA 48 V resistive
    1000000 cycles AC-14 110 VA 220 V inductive
    1000000 cycles AC-15 110 VA 220 V inductive
    150000 cycles AC-14 110 VA 110 V inductive
    150000 cycles AC-15 110 VA 110 V inductive
    1500000 cycles AC-14 50 VA 110 V inductive
    1500000 cycles AC-15 50 VA 110 V inductive
    2000000 cycles AC-14 24 VA 48 V inductive
    2000000 cycles AC-15 24 VA 48 V inductive
    3000000 cycles AC-14 50 VA 220 V inductive
    3000000 cycles AC-15 50 VA 220 V inductive
    500000 cycles AC-12 110 VA 48 V resistive
    500000 cycles AC-12 220 VA 110 V resistive
    500000 cycles AC-14 24 VA 24 V inductive
    500000 cycles AC-15 24 VA 24 V inductive
    5000000 cycles AC-14 10 VA 110 V inductive
    5000000 cycles AC-14 10 VA 220 V inductive
    5000000 cycles AC-14 10 VA 48 V inductive
    5000000 cycles AC-15 10 VA 110 V inductive
    5000000 cycles AC-15 10 VA 220 V inductive
    5000000 cycles AC-15 10 VA 48 V inductive
    700000 cycles AC-12 50 VA 24 V resistive
    marking
    CE
    electrical connection
    Screw terminal block
    current consumption
    135 mA 24 V DC rack
    80 mA 5 V DC
    module format
    Standard
    product weight
    0.38 kg
    Environment
    dielectric strength
    2000 V 50/60 Hz 60 s
    standards
    UL 508
    89/336/EEC
    CSA C22.2 No 213 Class I Division 2 Group B
    CSA C22.2 No 213 Class I Division 2 Group C
    CSA C22.2 No 213 Class I Division 2 Group D
    IEC 61131-2
    92/31/EEC
    73/23/EEC
    CSA C22.2 No 213 Class I Division 2 Group A
    93/68/EEC
    CSA C22.2 No 142
    product certifications
    ABS
    DNV
    RINA
    LR
    BV
    GL
    RMRS
    ambient air temperature for operation
    0...60 °C
    ambient air temperature for storage
    -25...70 °C
    relative humidity
    10...95 % without condensation for operation
    5...95 % without condensation for storage
    operating altitude
    0...2000 m
    protective treatment
    TC
    IP degree of protection
    IP20
    pollution degree
    2
    Offer Sustainability
    RoHS (date code: YYWW)
    REACh
    Product end of life instructions
    Need no specific recycling operations
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    Certificate
    Date
    Size
    Add to My Documents
    Date 2018/08/06
    Size 80.1 KB
    UL_E486184_NRAQ-NRAQ7_ALL_JUN2018
    Date 2018/08/06
    Size 160.6 KB
    Date 2018/08/06
    Size 173.2 KB
    Declaration of conformity
    Date
    Size
    Add to My Documents
    Date 2018/08/06
    Size 478.2 KB
    Date 2018/06/19
    Size 1.9 MB
    Marine certificate
    Date
    Size
    Add to My Documents
    Date 2018/05/23
    Size 78.9 KB
    Date 2018/01/17
    Size 164.4 KB
    Date 2018/01/17
    Size 1.6 MB
    Date 2018/01/17
    Size 750.3 KB
    Date 2018/01/17
    Size 785.6 KB
    BV Marine Certificate PREMIUM PLCs
    Date 2018/01/17
    Size 255.4 KB
    Date 2018/01/17
    Size 183.1 KB
  • Technical FAQs

    No results found
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Standard and Extendable Racks for Modules Mounting
    Dimensions of Modules and Racks


    (1) With screw terminal block modules.

    (2) Maximum depth for all types of modules and their associated connectors.


  • Connections and Schema

    Discrete Relay Output 16-Channel Module for 3 A Thermal Current
    Wiring Diagram


    Precaution

    NOTE: In the event of pre-actuator supply voltage being obtained from a tri-phase network which is equal to or greater than 200 Vac, the pre-actuators must be supplied from the same phase.