For Masterpact air circuit breaker (ACB) of type NW or NT, what are the avilable trip unit types and what arethe main protection functions supported by these trip units ?
- For the Masterpact ACB of type NW or NT, the available trip units for these range are of the Micro logic type trip units.
- These Micro logic trip units are found in the following types:
1- Micro logic (2): used for basic protection which include (Long + Instantaneous) Protection supported.
2- Micro logic (5): used for basic protection Which include (selective zone feature + Long + Short + Instantaneous) protection supported.
3- Micro logic (6): used for selective protection (same as Micro logic 5) + earth fault protection.
4- Micro logic (7): used for selective protection (same as Micro logic 5) + earth leakage protection.
- These Micro logic trip units are found in the following types:
1- Micro logic (2): used for basic protection which include (Long + Instantaneous) Protection supported.
2- Micro logic (5): used for basic protection Which include (selective zone feature + Long + Short + Instantaneous) protection supported.
3- Micro logic (6): used for selective protection (same as Micro logic 5) + earth fault protection.
4- Micro logic (7): used for selective protection (same as Micro logic 5) + earth leakage protection.
Released for: Schneider Electric United Arab Emirates
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.