What is the Modubs Register for Digital Input 1 (DI1) for a 7650

Issue

What Modbus register should be used to read Digital Input 1 (DI1) on an ION7650 meter?

Product Line

PowerLogic ION7650

Environment

Modbus (RTU or TCP)

ION Setup or ION Designer

External SCADA/PLC/RTU

Cause

Not all ION modules have a hard‑coded Modbus register. DI1 on the ION7650 is one such case.

Resolution

  • Map the DI1 module’s State output to a Modbus Slave register, then read that Modbus holding register from your master.

Note

ION7650 is discontinued, the recommended Schneider Electric replacement  is ION9000 series.

Schneider Electric United Arab Emirates

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Change your cookie settings