What is the cable pinout (RJ45 to RJ45) to connect a Compact 258/265/275/285 PLC to a 174CEV30010/20?

Issue

A serial communication cable is required between a Compact 258/265/275/285 and a CEV 300 10/20.

Product Line

  • Compact 258/265/275/285
  • CEV 300 10/20

Resolution

Wire the cable according to the following pinout:

Compact 258/265/275/285SignalConnectionCEV 300 10/20Signal
Pin 1+5 V→Pin 2DTR
Pin 2DSR→Pin 1NC
Pin 3TX→Pin 3RX
Pin 4RX→Pin 4TX
Pin 5GND→Pin 5GND
Pin 8Chassis GND→Pin 8NC

In addition:

  • On the Compact 258/265/275/285 side, bridge pin 6 (RTS) and pin 7 (CTS).
  • On the CEV 300 10/20 side, bridge pin 6 (CTS) and pin 7 (RTS).