Seven steps blinking of ComAct LED means âPROM checksum errorâ.
Obviously the firmware of the CHS110 module became corrupted.
First the customer should try to download again the firmware.
If this doesnât help then the customer has to replace the CHS110 module.
It is important to have identical firmware versions on both CHS modules.
Follow the steps to download the firmware into the CHS module:
Repeat the procedure until step 5.
The device Crash Code must be 0000 now.
Obviously the firmware of the CHS110 module became corrupted.
First the customer should try to download again the firmware.
If this doesnât help then the customer has to replace the CHS110 module.
It is important to have identical firmware versions on both CHS modules.
Follow the steps to download the firmware into the CHS module:
- Use the tool âEXECLoaderâ. You will find it in the Concept package.
- Launch the EXECLoader and select the Communication Protocol (e.g. Modbus Plus), Click to button âNextâ.
- Enter the CPU target address, Select the Device Type âLocal Headâ and enter the slot number where the CHS is mounted, Click to button âNextâ.
- Select Operation âTransfer EXEC to Deviceâ and browse to the filename âQchsv###.binâ, Click to button âNextâ.
- The tool now displays the file properties and the device properties.
Note: The device Crash Code will be 6301 in case of PROM checksum error, Click to button âNextâ - The tool displays a summary, Click to button âTransferâ.
- Wait for the message âThe transfer operation completed successfullyâ,Click button to âCloseâ.
Repeat the procedure until step 5.
The device Crash Code must be 0000 now.