{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric Gulf Countries and Pakistan Website

Welcome to our website.
Search FAQs
What would cause the Altivar 312 drive to lose some of it's settings when switched from local to remote mode?
Issue:
Parameter loss when switching from local to remote mode on Altivar 312 drive.

Product Line:
Altivar 312

Environment:
All

Cause:
The drive was set in local mode and some parameter settings got changed unexpectedly.

Resolution:
The Altivar 312 drive is not intended to toggle temporarily between local and remote modes by holding the MOD button for 3 seconds,  Doing so will change the logic inputs assignments and Fr1 & Cd1 channels back to factory default

Schneider Electric United Arab Emirates

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: