How do we ACK alarms on an HMI from a PLC bit?

Issue:
Looking for a way to programmatically ACK alarm on the HMI from a PLC bit.

Product Line:
Vijeo Designer, Vijeo Designer Runtime

Resolution:
To allow a PLC bit to ACK all alarms displayed in the Alarm Summary, the following script call should be made in a Panel Action (on the same panel as the Alarm Summary).

<Alarm Group name>.ackAll();

Note: The action should be configured as Conditional and to execute when the PLC bit is "True".

The attached project makes use of a Panel Action that executes an AlarmGroup script when a PLC bit is "True".

Please see the attached project for the example.

Schneider Electric United Arab Emirates

Attachment(s)
RemoteAckFromPLC.zip [55.14 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Change your cookie settings