Does Control Expert (formerly Unity Pro) offer status words that can be used to determine the communication health of an ERIO drop ?

Yes, the following System Words will allow you to see the communication health between the CRP31200 and the CRA31200
%SW172-173   Referred to as ERIO Connection Status
0= Drop is not communicating
1= Drop is communicating


R-71117