What are the reasons for system fault code 49 on LTMR08MFM (Motor Management SYSTEM )

Fault Code 49 = Stop Checkback

The LTM R controller performs diagnostic tests that detect and monitor the proper functionality of control

commands.

There are 4 control command diagnostic functions:

 Start Command Check

 Run Check Back

 Stop Command Check

 Stop Check Back

Stop Check Back

The Stop Check Back causes the LTM R controller to continuously monitor the main circuit to ensure no

current is flowing. The Stop Check Back:

 reports a Stop Check Back fault or warning if average phase current is detected for longer than 0.5

seconds without a Run command, or

 ends, when a Run command executes

Actions that can be taken :

Check the following:

 relay outputs

 all wiring, including:

 control wiring circuit, including all electromechanical devices

 power wiring circuit, including all components

 load CT wiring.

After all checks are complete:

1 Reset the fault.

2 If the fault persists, cycle power and wait 30 s.

3 If the fault persists, replace the LTM R controller.

Schneider Electric United Arab Emirates

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Change your cookie settings