Can you set up the ATV630 and ATV930 Process drive to run a motor with voltage limitation?
Issue:
ATV630 and ATV930 drives to run a motor with voltage limitation

Product Line:
ATV630 and ATV930

Environment:
All

Cause:
Needs to limit the voltage coming out of the drive.

Resolution:



Hello,
Unfortunately the parameter [UCP] Voltage at constant power - which was available in ATV61/71 - doesn't exist in the ATV6xx/ATV9xx.
The only possible work around is the usage of the V/f 5-points characteristic.
Exemplary parameter setting:
[U1] = 115V and [F1] = 25Hz
[U2] = 230V and [F2] = 50Hz
[U3] = 230V and [F3] = 51Hz
[U4] = 230V and [F4] = 75Hz
[U5] = 230V and [F5] = 100Hz
Please consider that the nominal point of the motor data MUST be the last value on this V/f characteristic. The nominal motor voltage [UNS] >= [U5] and the nominal frequency [FRS] >= [F5]. The nominal speed must be calculated according to the adjusted nominal speed.
[UNS] = 230V, [FRS] = 100Hz, [NSP] = 2980 rpm.
An auto tuning function needs not to be performed. Due to the "wrong" motor data it makes no sense.

Schneider Electric United Arab Emirates

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Change your cookie settings