If any unbalanced load in the system, How the neutral CT will sense and trip the breaker ( 3200amps TP ACB mic6.0E Trip unit with neutral sensor) ?

The “insulation fault” current is calculated using the vectorial sum of currents of instrument CT* secondaries.
*The CT on the Neutral conductor is often outside the circuit-breaker.