How can we help you today?

What is the input disconnector on ATV650C25N4F Floor standing Variable speed drive, Altivar Process ? Is there an input load-break switch (can disconnect nominal current ) or a disconnector?

It is INS630 (3-pole 630A switch disconnector) that is used as an input switch-disconnector. It can be switched off under nominal current.