Easergy Micom P632 relay is displaying “SFMON: Wrong module Dig.Bus” error .What is the meaning of this error ?
Issue/description:
Meaning of this error “SFMON: Wrong module Dig.Bus” appear in Easergy Micom P632 relay
Product family:
Easergy Micom P632 relay
Resolution:
The device has been fitted with a wrong digital bus therfore this is checked using the module variant number this signal can also occur after a firmware upgrade to a version that is not compatible with the hardware.
1st device reaction with Warm restart & 2nd device reaction will be blocking.
If device is block permanent, please contact our local after sales team/ our customer care to support further.