Easergy MiCOM P14x relay is hanging when injecting three-phase current above 0.25 A, but works fine with single-phase injection. How can this be resolved?
Issue/description:
Easergy MiCOM P14x relay is hanging when injecting three-phase current above 0.25 A, but works fine with single-phase injection.
Product family:
Easergy Micom P14x relays
Resolution:
Please check no gap detection on/off. & disable no gap detection from the event record in the Record Control in the Easergy Micom device to solve this issue.
Kindly find attached the snapshot how to reach no gap in Micom P14x relays.
If you require any further assistance, please contact our Customer Care team.