Can you explain how VIP3xx relay work with VAP6 test box ?

Issue :
VIP3xx relay work with VAP6 test box

Environment/Product line:
VIP 300 relays

Resolution :
Basic concept is any trip testing with the VIP300 should be done with the VAP6 test box
and VIP300 uses a MITOP output to send tripping commands.

VIP300 MITOP output is a capacitor. This is supposed to be connected to a small coil which has enough energy to trigger a small mechanical switch which then triggers a CB Trip operation.
The MITOP output should not be used as a Trip Contact like what you would find on a Sepam 20 relay (example :O1 output)

Since it is a microprocessor-based relay, testing with a VAP6 box should be sufficient. As long as the relay trips when you follow the procedure in the manual,
there is not really any need to perform "tripping delay" tests.

Schneider Electric United Arab Emirates

Explore more
Product:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Change your cookie settings