Issue: 
Using the READ_REMOTE EFB to read data from located or unlocated variables in a Unity Quantum PLC
Product Line:
EcoStruxure Control Expert, Modicon Quantum
Resolution:
Yes. The READ_REMOTE block will read data from a remote Unity Quantum PLC that support the Data Dictionary feature In the Quantum PLC, Data dictionary must be enabled. You must also de-activating the type verification based on checksum comparison using the CTRL parameter. In the second word of the four word array variable for the CTRL, you must enter a value of 1 to de-activate.
Quantum PLC showing unlocated variables with data.

M580 with READ_REMOTE block receiving the unlocated data from the Quantum
 
 
Using the READ_REMOTE EFB to read data from located or unlocated variables in a Unity Quantum PLC
Product Line:
EcoStruxure Control Expert, Modicon Quantum
Resolution:
Yes. The READ_REMOTE block will read data from a remote Unity Quantum PLC that support the Data Dictionary feature In the Quantum PLC, Data dictionary must be enabled. You must also de-activating the type verification based on checksum comparison using the CTRL parameter. In the second word of the four word array variable for the CTRL, you must enter a value of 1 to de-activate.
Quantum PLC showing unlocated variables with data.
M580 with READ_REMOTE block receiving the unlocated data from the Quantum
Released for: Schneider Electric United Arab Emirates


Need help?
- Product Selector- Quickly and easily find the right products and accessories for your applications. 
- Get a Quote- Start your sales enquiry online and an expert will connect with you. 
- Where to buy?- Easily find the nearest Schneider Electric distributor in your location. 
- Help Centre- Find support resources for all your needs, in one place.