{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric Gulf Countries and Pakistan Website

Welcome to our website.
Search FAQs
How to make PLC Simulator work into a PC doesn't contain Control Expert ?

Steps to configure PLC Simulator:

1- Copy the PLC_Simulator folder from a machine where Control Expert is installed and place it in the virgin machine.
2- Export the registry from the machine where Control Expert is installed, import it in your virgin machine and install it.
Registry
3- Execute sim.exe in the Folder PLC Simulator.
4- PLC Simulator will appear on the taskbar. Right click and choose Options.
PLC simulator icon
5- In the Simulator Panel Options window click on ... next to Starting Application with password and open your .STA project.
Options
6- Click OK and open PLC simulator Panel by double clicking on the PLC Simulator icon on taskbar.
Panel
7- Notice that Run LED is blinking and Simulator is in IDLE state.
8- Click Reset button to put the PLC in Run mode
Panel
9- Important points to remember is that the PLC project must be configured in Simulator mode and also Automatic start in Run must be enabled.

Schneider Electric United Arab Emirates

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: