ION Setup - "Network configuration seems corrupted" error
Issue
After logging into ION Setup, the following error messaged is displayed: "Network configuration seems corrupted. Do you wish to load the backup copy?"
Product Line
ION Setup
Cause
Due to a previous crash, interruption, or unsuccessful save, the network configuration files can sometimes become corrupted.
Resolution 1
Click Yes to see if it successfully loads the network configuration.
Resolution 2
If there is access to an existing Power Monitoring Expert (PME) 2020 or later installation, refer to this article to import the device list from PME.
Resolution 3
Try looking for manual backups of the network configuration files:
- In File Explorer, go to View > check Hidden Items:
- Look for renamed copies of DEVINFO.DAT, IONSETUP.DAT, and SITEINFO.DAT. There may be some present in manually created folders in the C:\ProgramData\Schneider Electric\ION Setup folder or in other folders/drives. To restore:
- Close ION Setup.
- Move the files to the C:\ProgramData\Schneider Electric\ION Setup folder.
- Rename the files to DEVINFO.DAT, IONSETUP.DAT, and SITEINFO.DAT respectively.
Resolution 4
Manually recreate the device network. To facilitate this:
- Manually add one device of each type, and at least one Ethernet site and one Ethernet Gateway site (if applicable). Refer to this article for the steps to add a device.
- Open File > Export Network.
- Open the exported .csv using Excel.
- Use Excel to populate the list with remaining devices and/or sites, following the formatting of the exported .csv.
- Save the .csv and close Excel.
- In ION Setup, open File > Import Network.