Flusarc 36 kV
Secondary Gas-Insulated Switchgear up to 36 kV
Features
| > Services |
- Standard : IEC 62271-200
- Rated voltage : Up to 36 kV
- Frequency : 50 or 60Hz
- Rated current busbar : 630A
- Busbar system : Single
- Short circuit rated current : 20kA 1 sec
- Internal Arc Classification :20kA AFLR with options
- Loss of service continuity : LSC 2
- Partition class: PM
Note: 24 kV performance is no more commercialised
Benefits
- Safety & Reliability : Internal arc compliant in accordance to standards with advanced relaying and protection options, direct earthing of the whole structure, total segregation, mechanical interlock
- Continuity service: low gas pressure, not affected by external environment
- Outdoor: there is an outdoor version
- Connected : new smart solutions in compliance with latest cybersecurity norms with scalable options such as network management , condition monitoring , power management , remote
Applications
- Transformer substations for onshore Wind Farms, in tower or kiosk installation
- Power Substations for Photovoltaic plants, inside kiosk or outdoor installation
- Public and private distribution networks, indoor or outdoor installation
- Transformer substations for Railways, CIB and O&G segments