Unity Pro v10/11 launching simulator causes error "Debugger process not created or not ready!" followed by "This isn't a valid PLC address, or PLC is busy, or media is off."
Issue:
This error occurs when trying to connect to the simulator. It usually occurs when being run on an unqualified OS.
Resolution:
Unity Pro v10/11 has not been qualified for Windows XP sp3.
However, the user can go to C:\program files\Schneider Electric\Unity Pro\PLC_Simulator and run debugger.exe.
This may correct the problem.
This error occurs when trying to connect to the simulator. It usually occurs when being run on an unqualified OS.
Resolution:
Unity Pro v10/11 has not been qualified for Windows XP sp3.
However, the user can go to C:\program files\Schneider Electric\Unity Pro\PLC_Simulator and run debugger.exe.
This may correct the problem.
Released for: Schneider Electric Belgium


Need help?
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.