how to avoid restoring all factory setting of the ATV32 behind a during the Boot-up?

Some STB Network Interface Module sends during the Boot-up the SDO parameter (1011:01) to restore all manufacturing parameters.
As the Boot-up can't be setting in STB NIM, we can avoid this if needed by setting the ATV32.
To reject the SDO parameter (1011:01) the bit7 of the Application Hidden Word AP01 have to be activated.
see pdf for the "how to activate the bit 7".