Why does the ATV630 drive trip on EPF2 Fault after installing the BACnet Card?
Issue:
ATV630 getting an EPF2 Fault after installing the BACnet Card.
Product Line:
ATV600, ATV630, ATV660
Environment:
All
Cause:
NA
Resolution:
Check the Profile Setting. If it is set for I/O profile then change it to Separate or Not Separate. However, changing I/O profile puts you back to factory settings. Therefore, all the VFD settings have to be programmed again.
ATV630 getting an EPF2 Fault after installing the BACnet Card.
Product Line:
ATV600, ATV630, ATV660
Environment:
All
Cause:
NA
Resolution:
Check the Profile Setting. If it is set for I/O profile then change it to Separate or Not Separate. However, changing I/O profile puts you back to factory settings. Therefore, all the VFD settings have to be programmed again.
Released for: Schneider Electric Belgium


Need help?
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.