Does the ATS48 offer phase reversal protection?
Issue:
Protection against phase inversion with ATS48.
Product Line:
Altistart 48, ATS48
Environment:
All models
Cause:
NA
Resolution:
The ATS48 does have a phase inversion protection feature, but it needs to be activated. In the PrO menu, set PHr = 123 or 321 to match the required rotation. If the rotation does not match, the ATS48 will fault with PIF code.
Protection against phase inversion with ATS48.
Product Line:
Altistart 48, ATS48
Environment:
All models
Cause:
NA
Resolution:
The ATS48 does have a phase inversion protection feature, but it needs to be activated. In the PrO menu, set PHr = 123 or 321 to match the required rotation. If the rotation does not match, the ATS48 will fault with PIF code.
Released for: Schneider Electric Belgium




Need help?
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.