What is the scaling of PID feedback value when the feedback is taken from pulse input on LI5?

The scaling between feedback value (RPF parameter) and the pulse input when assigned as PID feedback (PIF=RP) dependss on following parameters:
- min PID feedback setting (PIF1)
- max PID feedback setting (PIF2)
- min pulse input frequency (PIL)
- max pulse input frequency (PFR)
The conversion between pulse input value and PID feedback is linear and PIL corresponds to PIF1 and PFR corresponds to PIF2.

For example, PIL=5kHz, PFR=20kHz, PIF1=0, PIF2=10000
Then
- at input frequency below 5kHz, the RPF=0
- at input frequency 10kHz, the RPF=3333
- at input frequency 15kHz, the RPF=6666
- at input frequency 20kHz, the RPF=10000

Schneider Electric Belgium

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings