What is the acceptable tolerance for the stripping length of a cable to be connected to the bare cable connectors of the Compact NSX?
For a correct installation of the wires to the bare cable connectors of Compact NSX, the cables must be stripped to the length indicated in the supplied instruction sheet, with the accepted tolerance of -0mm / +2mm.