What causes a CbF [Circuit Breaker Error] fault on an ATV340 series drive and how do I correct it?
Issue:
How can you resolve a CbF [Circuit Breaker Fault] on an ATV340 series drive?
Product Line:
ATV340
Environment:
Circuit Breaker Logic function is being used.
Cause:
Resolution:
How can you resolve a CbF [Circuit Breaker Fault] on an ATV340 series drive?
Product Line:
ATV340
Environment:
Circuit Breaker Logic function is being used.
Cause:
The DC bus voltage level is not correct compared to the circuit breaker logic control (start or stop pulse)
after the configured timeout [Mains V. time out] LCt.
Resolution:
Verify the circuit breaker logic control (pulse time for start and stop).
Verify the mechanical state of the circuit breaker.
Released for: Schneider Electric Belgium


Need help?
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.