Compact NSX and NSXm 2021 series - do they comply with the 6mA continuous current requirement? What standard do these RCDs - Residual Current Devices - comply with?

Article available in these languages: French, Dutch

Power products including NSX and NSXm 2021 Series with Micrologic 4.1, NSX with micrologic 4/7 and Vigi add on, are not governed by residential standards such as IEC 61009 and 61008, but rather by IEC 60947-2 , annex B.

Yes they all comply with requirement of 6 mA DC current (Type A Residual current protection) as stipulated in standard IEC 60755 (that is references in IEC 60947-2).

It is written in the catalog: https://download.schneider-electric.com/files?p_enDocType=Catalog&p_File_Name=LVPED221001EN+ComPacT+NSX&NSXm+AC++.pdf&p_Doc_Ref=NSX_NSXm_Catalog_2021

on pages B-23, B-14, B-16 and B-18.

For NSX with micrologic 4/7 it is not explicitly written, but simply these are the requirements of the IEC 60947-2 standard.

Schneider Electric Belgium

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings