How can we help you today?

How can you program a Jog function, in a ATV212 drive?

Issue:

Programming a Jog function, in a ATV212 drive.

Product Line:

ATV212

Environment:

Jog

Cause:

n/a

Resolution:

This drive does not have a jog function, in the menus. You would need to program a Preset Speed. Go to F113 (RES) and set to 6 and set SR1 to 10 ( or whatever jog speed you need?). When F and RES goes high, should run at the jog speed.

Schneider Electric Belgium

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center