How can I set up ATV320 for mixed controls using Terminals and Modbus?
Issue:
How can I set up ATV320 drive for Terminal Start/Stop Control and Modbus Speed Reference?
Product Line:
ATV320, Altivar 320
Environment:
All
Cause:
NA
Resolution:
LI1 FWD (2-wire control)
CHCF SEP
Ref 1 Modbus
Cd1 is Terminal control
How can I set up ATV320 drive for Terminal Start/Stop Control and Modbus Speed Reference?
Product Line:
ATV320, Altivar 320
Environment:
All
Cause:
NA
Resolution:
LI1 FWD (2-wire control)
CHCF SEP
Ref 1 Modbus
Cd1 is Terminal control