"Software Protection Failure. No key found or no license available from network" System services "Login Aborted" in service mode

Issue

Running Power Operation in service mode results in the below error.

Software protection failure, no key found

Product Line

Power Scada Operation 2020

Power Scada Operation 2020 R2

Power Scada Operation 2021

Ecostruxure Power Operation 2022

Ecostruxure Power Operation 2024

Environment

Windows Services

Setup Editor

License Configuration Tool

Runtime Manager

Cause

Autologin mode being disabled is necessary in order to have the service account run the Runtime Manager. With autologin mode disabled, a login form is generated which the service cannot enter the credentials for. This causes the system to hang and login to be aborted.


Resolution

Reference the [Client]AutoLoginMode parameter to make the best decision for how to start the Runtime Manager. If Power Operation is to be run in service mode, it is best to run in AutoLogin Mode.

Schneider Electric Belgium

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings