How can we help you today?

Where can I find the Modbus registers of PowerTag energy sensors?

FAQ – PowerTag Modbus Registers (PowerTag Link)

❓ Where can I find the Modbus registers of PowerTag energy sensors?

The Modbus registers for PowerTag energy sensors are documented in the PowerTag Link User Guide, specifically in the section:

“PowerTag Energy Sensors Modbus Registers”.

👉 Direct link:

This section contains the complete register tables used for Modbus communication via the PowerTag Link gateway.

❓ What information is available in these Modbus registers?

The Modbus tables provide access to key electrical measurements, including:

  • Current measurements (per phase)
  • Voltage measurements (phase-to-phase and phase-to-neutral)
  • Power measurements (active, reactive, apparent)
  • Power factor and energy values

For example:

  • Registers around 3000–3006: RMS current per phase
  • Registers around 3020–3032: Voltage values
  • Registers around 3054–3076: Power values [productinfo.se.com]

❓ Do all PowerTag devices use the same registers?

Not exactly.

Each register indicates which devices it applies to:

  • A → PowerTag Energy 63
  • M → PowerTag Energy M250 / M630
  • R → PowerTag Energy F160 / Rope

This is clearly shown in the “Applicable Devices” column in the tables. [productinfo.se.com]

❓ How do I interpret the Modbus register table?

Each register entry includes:

  • Register number and address
  • Data type (e.g., Float32, INT64)
  • Unit (A, V, W, etc.)
  • Read/Write information
  • Scaling factor (if applicable)

For example:

  • A scaling factor defines whether the value must be multiplied or divided to get the real measurement. [productinfo.se.com]

❓ How do I read these registers via Modbus?

PowerTag Link communicates via Modbus TCP/IP using a client/server model.

Typical function codes:

Each wireless PowerTag device is assigned a Modbus address (1–247) via the gateway configuration. [productinfo.se.com]

❓ Where are the energy (kWh) registers located?

Energy values (such as total active energy) are available in dedicated registers (e.g. around the 3200 range), often using 64-bit (INT64) format.

⚠️ Note:

  • Values are typically stored in Wh, so conversion to kWh may be required.

❓ Do I need the PowerTag Link gateway to access Modbus registers?

Yes.

The PowerTag Link gateway is required because:

  • It collects wireless data from PowerTag sensors
  • It exposes this data via Modbus TCP/IP

Without the gateway, Modbus communication is not available.

❓ Where can I find all Modbus register categories?

The user guide organizes registers by device type:

  • PowerTag Energy sensors
  • PowerTag control modules
  • HeatTag sensors
  • Gateway/system registers

See the overview here:

✅ Summary

  • The Modbus registers are available in the PowerTag Link User Guide
  • The relevant section is**“PowerTag Energy Sensors Modbus Registers”**
  • Registers cover all key electrical measurements and follow standard Modbus structure
  • Access is done via the PowerTag Link gateway (Modbus TCP/IP)

Schneider Electric Belgium

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings