Machine Expert V2.3/2.5 - Password Expiration: Default Setting and Configuration
Issue / Symptoms:
Communications using login/password no longer works.
For example, HMI may be disconnected from the machine.
Same for OPC UA, FTP, Web Visu, Web Server connections.
When connecting from Machine Expert, a popup window is displayed saying that the PLC password has expired and requiring setting a new password.
This issue is due to the Password Expiration setting that was introduced in Machine Expert V2.3 and V2.5.
There is no way to determine the default expiration period when the setting remains unchanged from its default value.
Product lines:
M241, M251 and M262 controllers programmed with Machine Expert V2.3 or V2.5.
Resolution:
To confirm the default value for the Password Expiration Timeout Days that is configured in a specific Machine Expert controller, it is required to connect to the specific controller for which this value has not been changed.
For the M241, M251 and M262 controllers, the default value is 365 days. It is possible to change it from 0 to 1000 days.
There are different possibilities to prevent the expiry of the password from accessing the controller:
- From Machine Expert
- Via FTP connection
- By using an SD card
See attached documents.
Note:
In case the password is already expired, only a connection from Machine Expert allows renewing it.
Nevertheless, a solution by using the Clone feature via SD card can be also used but an additional PLC and Machine Expert are required.
See attached procedure.
Released for: Schneider Electric Belgium
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.