Issue
Links to access the raw status data of Symmetra intelligence modules are missing in the Network Management Card (NMC) interface
Product Line
- Network Management Card 2 - AP9630/AP9630CH, AP9631/AP9631CH, AP9635/35CH
- Symmetra UPS systems
Environment
- Firmware version AOS 6.4
- All serial numbers
Resolution
Links to access the raw status information of the Symmetra intelligence modules are missing from AOS 6.4. This will be resolved in a future release, and this KB article will be updated when a fixed version is available. It is possible to access the raw status information of the intelligence modules by modifying the URL as shown in the steps :
Step 1 - Navigate to the IM information page (Status --> UPS --> Intelligence modules)
Step 2 - Select "View All Battery Raw Status Data" at the bottom of the page
Step 3 - Modify the end of the URL from "uprawbatt.htm" to "upraw.htm", and press enter to reload the page
This page will show all raw status information for the Intelligence Modules, Power Modules and any connected Battery Frames
Released for: Schneider Electric Egypt and North East Africa
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center