How to troubleshoot a Rack Inlet High Temp Alarm

Article available in these languages: Spanyol

Issue:

Rack inlet high alarm

Product line:

Inrow

Environment:

Data Center Inrow

Cause:

Temp threshold is to low, sensor is misplaced, sensor is defective

Resolution:

Check the sensor threshold, check placement of sensor. Threshold should be at least 5 degrees above max normal temp to avoid nuisance alarms. The sensor should be placed in the front of the server rack at least 6 inches from front of the server.  Ensure blanking panels are in place and ensure any gaps in the rack are addressed. Check the sensor reading to ensure it is within tolerance and not reading Err. Which could mean moisture has infiltrated the sensor, the connection is compromised or with sensor wire may be pinched.

Schneider Electric Hungary

Tudjon meg még többet
Tartomány:
Tudjon meg még többet
Tartomány:

Segítségre van szüksége?

  • Termékválasztó

    Gyorsan és egyszerűen megkeresheti az alkalmazásához illeszkedő termékeket és tartozékokat.

  • Árajánlat kérése

    Kezdje meg vásárlását online, és szakértőnk felveszi Önnel a kapcsolatot.

  • Hol vehetem meg?

    Találja meg egyszerűen az Önhöz legközelebbi kereskedelmi partnerünket.

  • Help Center

    Egyetlen helyen megtalálhatja az igényeinek megfelelő támogatási információforrásokat.

  • Termékdokumentációk
  • Szoftverletöltések
  • Termékválasztó
  • Termékkiváltás és -csere
  • Súgó és ügyfélkapcsolati központ
  • Irodakereső
  • Árajánlat kérése
  • Hol kapható?
  • Állások
  • Vállalati profil
  • Etikátlan magatartás bejelentése
  • Hozzáférhetőség
  • Hírek
  • Befektetők
  • EcoStruxure
  • Álláskeresés
  • Blog
  • Adatvédelmi szabályzat
  • Cookie-kra vonatkozó szabályzat
  • Cookie-beállítások módosítása