Smart-UPS VT-G3500; Load does not turn on automatically after an outage/shutdown

Article available in these languages: Spanyol


Issue:
Load does not turn on automatically after an outage/shutdown


Product line:
Smart-UPS VT-Galaxy 3500


Environment:
All Product models, all serial numbers


Cause:
The system is set to not auto start by default


Resolution:
You can set the load to turn on automatically after an outage from the PowerView display.

1. Go to Setup menu
2: Select System
3: Select Auto Start
4. Change value to On

This may take one reboot of the UPS to take affect, and you will need to turn on the load manually then.  After that first reboot it should automatically turn on in the future.

Schneider Electric Hungary

Tudjon meg még többet
Tartomány:
Tudjon meg még többet
Tartomány:

Segítségre van szüksége?

  • Termékválasztó

    Gyorsan és egyszerűen megkeresheti az alkalmazásához illeszkedő termékeket és tartozékokat.

  • Árajánlat kérése

    Kezdje meg vásárlását online, és szakértőnk felveszi Önnel a kapcsolatot.

  • Hol vehetem meg?

    Találja meg egyszerűen az Önhöz legközelebbi kereskedelmi partnerünket.

  • Help Center

    Egyetlen helyen megtalálhatja az igényeinek megfelelő támogatási információforrásokat.

  • Termékdokumentációk
  • Szoftverletöltések
  • Termékválasztó
  • Termékkiváltás és -csere
  • Súgó és ügyfélkapcsolati központ
  • Irodakereső
  • Árajánlat kérése
  • Hol kapható?
  • Állások
  • Vállalati profil
  • Etikátlan magatartás bejelentése
  • Hozzáférhetőség
  • Hírek
  • Befektetők
  • EcoStruxure
  • Álláskeresés
  • Blog
  • Adatvédelmi szabályzat
  • Cookie-kra vonatkozó szabályzat
  • Cookie-beállítások módosítása